Selection Criteria
An assessment should be made
of the anticipated processes before a fume hood is selected to ensure
that users are adequately protected and the fume hood may be expected
to perform reliably.
These include the following:
- chemical attack;
- chemical toxicity;
- radioactive contamination;
- solvent attack;
- thermal stress;
- adsorption and absorption
of hazardous substances;
- explosions;
- fire;
- mechanical stress, e.g.,
vibration; and workplace environment.
Manufacturers Information
The following information should
be obtained from the manufacturer:
The fume hood must meet the minimum design criteria outlined in CSA Z316.5-94. and meet or exceed performance standards specified by ANSI/ASHRAE 110-1995 .
Used Fume Hoods
Use fume hoods must be approved by UW design section in conjunction with the Safety Office. Persons wishing to purchase previously used fume hoods are responsible for obtaining the following:
Decontamination Certificates from previous owners for:
- Radioactive contamination
- Biological contamination
- Chemical contamination
Information from the manufacturer:
- type of fume hood and exhaust
system;
- identification of all materials
of construction;
- dimensioned drawings of the
fume hood;
- results of the evaluation
in a test facility;
- operating and maintenance
instructions for all the equipment; and
- any specific limitations
on use.
Construction
Materials
All materials, including service
fittings and exhaust systems, shall be resistant to the chemicals and
substances specified as permissible for use within the fume hood.
- tempered plate -glass shall
be used.
- plastic is used, it shall
be a fire-retardant grade.
- coatings and finishes shall
be fire resistant.
- sealants and adhesives shall
exhibit good chemical and thermal resistance and suitable mechanical
properties.
Cabinet
- work surface shall have raised edges (1/2") and sealed to help
contain any spills.
- work surface shall be strong enough to bear the weight of any necessary
apparatus.
- sash openings shall incorporate airfoils to inhibit refluxing of air
at the face opening.
- the rear and top of the hood shall be supplied with 3 baffles, the
top and bottom being adjustable.
Electrical
- Fume hoods and exhaust systems shall comply with the applicable requirements
in CSA Standards C22.1 and C22.2 No. 151 or C22.2 No. 1010.1.
Note: The risk assessment may identify the fume hood and immediate surroundings
as hazardous locations requiring special (e.g. explosion-proof) electrical
equipment. The criteria for determining the degree of hazard and the
appropriate type of electrical equipment are provided in Section 18
of the Canadian Electrical Code, Part 1. In order to obtain proper electrical
classification of hazardous locations, ft is necessary to contact the
local authority having this jurisdiction.
- All electrical receptacles shall be readily accessible and external
to the fume hood interior.
- A ground fault interrupter should be used in the electrical power
supply where necessary.
Services
- All plumbing and electrical services shall be installed such that
they can be readily connected or disconnected, either by design of the
assembly or via an access panel in the fume hood interior or exterior.
- All valves shall be accessible for maintenance.
- All service fixture controls (e.g. gas, air, water, vacuum) shall be
external to the fume hood, clearly identified and within reach.
- All service fixtures within the workspace shall be corrosion resistant
or have a corrosion resistant finish.
- If water service is provided, the fume hood shall have provisions
for a suitably designed drain.
- Light fixture(s) mounted exterior to the fume hood liner shall be
protected from the fume hood interior by a sealed, transparent, impact-resistant
vapour shield.
- Light fixture(s) mounted inside the fume hood liner shall be protected
against corrosion.
- Light fixture(s) mounted inside the fume hood liner shall be vapour
proof.
- Light fixture(s) shall be capable of providing an il luminance at
the work surface consistent with the level required by Part VI of the
Canada Occupational Safety and Health Regulations.
Alarms
- A fume hood shall have an audible and visual alarm to indicate to
the user when the air flow deviates from the set point.
- The alarm shall be readily visible to the user during use of the fume
hood.
- Only authorized personnel shall be able to adjust the alarm set point.
- The alarm shall remain functional in the event of loss of mains electrical
power.
- Battery power supplies shall have a low charge indicator.
Exhaust System
General
Exhaust duct, fan, and scrubber
materials should be chosen based on compatibility with the materials handled
in the fume hood, as well as compatibility with the installation and maintenance
of the fume hood.
Exhaust Ducts
- Exhaust ducts should be constructed to SMACNA Seal Class B Standards
as a minimum.
- Exhaust ducts should be maintained under negative pressure.
Note: This will reduce the possibility of
contaminants leaking into the building. Even with a remotely located.
exhaust fan, the discharge side of the exhaust fan provides a positive
pressure.
- Fume hoods with integral fans shall have appropriately constructed
exhaust ducts.
- Each fume hood should be separately ducted to a point outside the
building. Perchloric acid fume hoods shall be separately ducted to a
point outside the building. Radioisotope fume hoods shall be separately
ducted to a point outside the building, unless located in the same room.
- The exhaust stack shall be located so as to ensure acceptable dilution
and dispersion of exhaust air and to preclude exhaust re-entry through
air intakes and building openings.
- The exhaust stack shall not be fitted with devices, which deflect
the effluent or reduce the discharge velocity.
Note: Rain protection by weather caps and
swan neck ducts are examples of such devices.
- Thermoplastic materials shall not be used for duct work.
- Fire-retardant material or carbon steel with an acid-resistant coating
may be used for general chemical applications.
- Stainless steel ducts shall be used for perchloric acid fume hoods.
- Corrosion-resistant ducts shall be used for radioisotope fume hoods.
- Vitrified clay pipes with sealed joints may be used for acidic, alkaline,
and plating solutions
Exhaust Fan
- Exhaust fans should be positioned as close as possible to the termination
(discharge end) of the duct, preferably on the roof.
Notes:From the fan position to the termination
of the duct, the internal pressure is positive and any leaks in the
duct will allow the escape of contaminants from the duct into the
surrounding spaces.
Consideration should be given to protecting the fan from the effects
of adverse weather conditions.
- The fan motor should be mounted outside the exhaust duct for easy
access and to avoid contamination of the motor. Appropriate shaft seals
shall be employed.
- Glass fibre, PVC, or equivalent fans shall be used for highly corrosive
conditions.
- Coated steel, glass fibre, or PVC fans may be used for low to moderately
corrosive conditions.
- Fans shall be sized to provide adequate exhaust air flow. The static
pressure losses of the fume hood and associated duct work shall be included
in the determination of fan size.
Types of Fume Hood
- Bypass
- Ductless
- Walk in
- Glove
- Biological
Special Design Criteria for
Perchloric Acid Fume Hoods
Perchloric acid fume hoods shall
comply with the criteria described in this standard and with
The following additional requirements:
- Fume hoods designed for and used with perchloric acid shall be identified
by a prominent and permanent label indicating suitability for use with perchloric
acid procedures.
- All exposed parts of the fume hood interior shall be suitable for
use with perchloric acid.
- The work surface shall be watertight and furnished with a raised lip
to contain spills and wash down water.
- The fume hood shall be provided with a water spray (wash down) system
for rinsing the duct work from point of discharge to the fume hood collar
and also the area behind the baffle.
- The duct work shall be self-draining with no horizontal sections.
- Service fitting controls for internal outlets and for the wash down
systems shall be external to the fume hood, clearly identified, and
within easy reach.
- The baffle shall be removable to allow periodic inspection for damage/corrosion.
- The fume hood shall be constructed of nonporous, inorganic, acid-resistant,
non reactive material, and shall be impervious to perchloric acid.
- Specially designed fans shall be used.
Installation
Location
Fume hoods shall be installed
according to the manufacturer's instructions.
- Fume hoods should be located out of the normal, traffic pattern and
away from interfering room air currents.
- Seated work stations shall not be located directly opposite fume hood
openings.
- The distance between the side of the fume hood and a wall or large
architectural obstruction (e.g., an architectural column) protecting beyond
the plane of the sash should be at least 0.3 m
Note: The adjoining wall may present a partial
obstruction which may affect intake air flow.
- The user's unobstructed personal work area should extend at least
1.5 m from the face of the fume hood.
- The distance between the sash and an opposing wall or other obstruction
likely to affect the air flow should be at least 2.0 m.
- Fume hoods should not be installed face to face nor opposite a biological
safety cabinet unless the distance between them is at least 3.0 m .
- The distance between the sash of the fume hood and a doorway should
be at least 1.5 m.
- The distance between the side of the fume hood and a doorway should
be at least 1.0 m
- Any room air supply diffuser should not be within 1.5 m of the sash
and shall not affect fume hood performance.
Exhaust Duct Installation
- The exhaust duct should be self-draining and proceed to the discharge
point with as few horizontal sections as possible.
Note: This is to minimize areas in which condensates or liquids coming
in from the discharge point can collect.
- Ducts shall be sealed, according to SMACNA Seal Class B Standards,
to prevent leakage
- The following information shall be recorded when the fume hood and
exhaust system is installed:
- "as built" drawings showing the complete installation;
- identification of the materials of construction;
- operating and maintenance instructions; and
- make, model, and serial number.
Commissioning
After installation UW Plant
Operations Design Section shall notify Plant Operations Maintenance Section
to commission the fume hood.
Commissioning shall include, but not be limited to, determinations of
the following:
- electrical safety;
- adequate lighting;
- noise level;(less than 55 dBA)
- the functioning of components and services; and
- field performance test results as specified in Clause 11.4 CSA Z316.5-94.
Field Test
- All test and measurement equipment shall be accurate and properly
calibrated as specified in CSA Standard CAN/CSA-Q419.
- The building ventilation system shall be operating correctly, the
room doors and windows in their normal position, and all other fume
hoods and exhaust systems operating at design conditions.
- Fume hoods shall normally be tested empty. However, in exceptional
circumstances, it may be essential for the safety of the verifier to
test a fume hood with fixed equipment in place.
- Face velocity shall be measured and the test results shall be compared
with the values provided by the manufacturer. The test results shall
be documented and provided to the user.
- The sash is open to a normal working height.(approximately 18")
- The minimum face velocity is between 100 to 120 fpm.
- The maximum sash working height is marked
Sash Operation
- Sash operation shall be smooth and easy throughout its travel.
- Sash(es) shall be operable from either end with one hand.
- Sash counterbalances should operate without interference or restriction.
- Vertical rising sashes shall hold at any set height without creeping
up or down.
- All adjustable baffles shall operate freely,'without binding or restriction.
- The alarm shall function properly and indicate unsafe conditions when
the air flow is restricted.
Maintenance
General
Before an inspection or any
maintenance work is performed, the extent of hazards resulting from contaminated
surfaces shall be assessed and any necessary personal protective equipment
or clothing shall be used. The laboratory supervisor is responsible for
removal of any material located in the fume hood.
Wash down systems should-be regularly
used and properly maintained.
Note: This is to facilitate the removal of corrosive condensates from
the interior surface before damage occurs.
Twelve Month Maintenance
Every twelve months, the following
maintenance operations will be performed By UW Plant Operations Maintenance
Sections:
- inspect the fans, motors, drives, and bearings for correct operation;
- test the controls of the services to the fume hood for proper operation;
- inspect the fire damper and the release mechanism;
- measure the fume hood face velocity and compare to fume hood specifications,
correct
as necessary;
- test the operation of the air flow alarm; and
- repair defects and lubricate as necessary.